Description
For use in connecting control equipment to mechanical assembly lines, conveyor belts, transportation systems and manufacturing lines.The screen, comprising of thin,tinned copper wires, is designed to transmit control signals without any interference or noise.These cables have a thinner structure compared to other control cables, are flame retardant and may be used where toxic gas emissions must be avoided.
Cable structure | |
Conductor | Twisted copper wires; IEC 60228 Class 5, TS DIN 60228 Class 5 |
Insulation | HFFR, HI2, VDE 0207-23 |
Insulation Colors | According to TS/DIN EN 50334, white numerical code on black core along with yellow and green core.No yellow or green core for OZ |
Stranding | Veins are twisted in layers at regular intervals. |
Internal Sheath | HFFR, RAL 7001 Grey |
Screen | Thin, tin plated copper wires |
Sheath | HFFR, HM2, VDE 0207-24 |
Technicial Specifications | |
Conductor Resistance | 0.50 mm² = 39 Ω/Km |
0.75 mm² = 26 Ω/Km | |
1.00 mm² = 19.5 Ω/Km | |
1.50 mm² = 13.3 Ω/Km | |
2.50 mm² = 7.98 Ω/ Km | |
4.00 mm² = 4.95 Ω/Km | |
6.00 mm² = 3.30 Ω/Km | |
10.00 mm² = 1.91 Ω/Km | |
16.00 mm² = 1.21 Ω/Km | |
Insulation Resistance | min. 20 MΩ.Km |
Operating temperature | Fixed Fixed Laying -30 ° C ~ + 70 ° C |
Movable Flexible -5 ° C ~ + 50 ° C | |
min. Bending Radius | Fixed Fixed Laying 8 x D |
Movable Flexible 15 x D | |
Operating voltage | 300 / 500 V |
Test Voltage | 2000V |
Flame Retardant Test | IEC 60332-1-2 & TS/DIN EN 50266-2-4 |
Smoke Density | IEC 61034-2 & TS/DIN EN 50268-2 |
Corrosive Gas Test | IEC 60754-1/2 & TS/DIN EN 50267-2-3 |
Reviews