Description
- EDS Conventional Fire Detection Panel
- 4 Regions
- Product Options Available from 2 Regions to 16 Regions
- Alphanumeric LCD Display
- Plastic box
- EN 54 Certified
| electrical | |||||
| AC Input | 220 + 10% - 15% | ||||
| Power consumption | <53W | ||||
| Cable Connection | 3 x 1.5 mm2 / 1 km | ||||
| Zone Wiring | 12 - 26 AWG (3.31 to 0.13 mm2 Twisted Pair Cable (max. 40Ω / 500 nF) / 1 km | ||||
| Siren End of Line Resistor | 15kΩ | ||||
| End of Line Resistance | 4.7kΩ | ||||
| Battery Fuse | Resettable | ||||
| Regional Insurance | Resettable | ||||
| Number of Regions | 2-4-8-12-16 | ||||
| Number of Outputs | one | ||||
| Alarm Relay Commutation Current | 2A - 30V DC max. | ||||
| Resistance Per Zone Circuit | 50 Ω max. | ||||
| Siren Output | 2 x short circuit protection / traceable | ||||
| Siren Output Power | 2x150mA max. (ECSI20; 15 pieces can be connected) +25 °C Voltage: -12 V DC max. Alarm Voltage: 28 V DC max. | ||||
| 24V Output | 28.5 V DC max. 21 V DC min. 100 mA max. 27.4 V DC nominal 25 °C | ||||
| Predefined User Passwords | (User 22), (Super User 99) and optional key | ||||
| Network Insurance | 0.5A delay | ||||
| Battery | 2 x 12 V DC 7 Ah | ||||
| Battery Low Voltage | 22V DC ± 0.5V | ||||
| Battery Charging Current | max. 0.4A | ||||
| Battery Charging Voltage | 27.2V ± 2% - 20° / -36mV/°C | ||||
| Stationary Voltage Level | <21V | ||||
| Internal Battery | Battery Place Available | ||||
| Battery Impedance | >2.5 Ω | ||||
| Frequency Changing | 132kHz | ||||
| Fluctuation | <200mV | ||||
| Class Conditions | 3k5 of IEC 60721-3-3 | ||||
| Storage Temperature | -20 to +70 | ||||
| IP Class | 30 | ||||
| I max | 208 mA 212 mA 232 mA 253 mA 280 mA | ||||
| I max b | 612 mA 594 mA 624 mA 644 mA 684 mA | ||||
| I min | 80mA | ||||
| Front Panel | 2 x 16 Alphanumeric LCD Display | ||
| Indicator Type | 7 LED Indicators | ||
| Indicators | Alarm, Mains, Battery, Fault, Siren Fault, System Fault, Disabled | ||
| Audio and Visual Warning | Available | ||
| Buttons | RESET SYSTEM, SIREN ON/OFF, PANEL MUTE, Direction Keys | ||
| Region Features | |||
| Zone Circuit Output Voltage | Maximum 25.17 V Nominal 24.65 V Minimum 18.96 V | ||
| Detector Alarm Reference Range | Zone Voltage 7.7 V - 17.2 V Zone Impedance 160 Ω - 735 Ω | ||
| Manual Alarm Reference Range | Zone Voltage 2.9 V - 7.5 V Zone Impedance 50 Ω - 155 Ω | ||
| Short Circuit Reference Range | Zone Voltage < 2.66 V Zone Impedance <45 Ω | ||
| Open Circuit Reference range | >14.7K | ||
| Material Body | Plastic | Metal | |
| Certificate | 1922-CPR-1577 | ||
| Operating temperature | -10 °C ~ +50 °C | ||
| Dimension | 303x307x115mm | 274x324x68mm | |
| Weight | 990g | 2400g | |
| Certificate | 1977-CPR-1577 | ||
| Certificates | |||
| Certificates | CE/ DEDAL | ||
| Approved organization number | 1922 | ||
| Dedal certificate number | 1922- CPR-1577 | ||
| Standard number | EN54-2 / EN54-4 | ||