Description
Cable structure |
|
Conductor |
IEC 60228 / Class 5
TS/DIN EN 60228 CLASS 5 electrolytic twisted copper |
Insulation |
Special halogen free
material resistant to fire |
Stranding |
Cores are twisted in
layers at regular intervals. |
Insulation Colors |
DIN 47100 |
Separating Wrapping |
PES TAPE |
Protective Sheath |
Glass fiber sheath |
Screen 1 |
AL-PEs TAPE |
Screen 2 |
Tinned copper braiding |
Sheath |
HFFR, HM4, VDE
0207-24, RAL 2003 Orange |
Technicial
Specifications |
|
Conductor Resistance |
0.14 mm² = 148 Ω.Km |
0.22 mm² = 96 Ω.Km |
|
0.25 mm² = 79.9 Ω.Km |
|
0.34 mm² = 56 Ω.Km |
|
0.50 mm² = 39 Ω.Km |
|
0.75 mm² = 26 Ω.Km |
|
1.00 mm² = 19.5 Ω.Km |
|
1.50 mm² = 13.3 Ω.Km |
|
2.50 mm² = 7.98 Ω.Km |
|
Insulation Resistance |
> 200 MΩ.Km |
Operating voltage |
0.14 mm² = 350 V |
≥ 0.22 mm² = 500 V |
|
Operating temperature |
-30°C ~ +80°C |
min. Bending
Radius |
Fixed Fixed Laying 6,5
x D |
Movable Flexible 15 x
D |
|
Flame Test |
IEC 60332-1-2 &
TS/DIN EN 50266-2-4 |
Smoke Density |
IEC 61034-2 &
TS/DIN EN 50268-2 |
Corrosive Gas Test |
IEC 60754-1/2 &
TS/DIN EN 50267-2-3 |
Insulation Continuity |
IEC 60331, VDE
0472-814 |
Mechanical Impact Fire
Resistance |
DIN EN
50200; PH30-PH60-PH90 |
Current Discontinuity
to the System |
DIN 4102-12
; E30-E90 |
Reviews
Be the first to review this item
There are no reviews yet