Description
These cables are halogen free flame resistant cables which can transfer energy for 180 minutes under fire conditions ( when stationary ). Additionally, they provide continuous current in the DIN 4102-12 test ofE30 and E90 for cables and systems.This cables are used in computer systemsand as control and signal cables in electronic control equipment.Notfor external or subterranean use.Tinned copper screen protects the cable from external electrical effects as well as wrapping the cores for protection.Ideal for use when toxic gas emissions must be avoided.This cables do not conduct flames.
Cable structure | |
Conductor | IEC 60228 / Class 5 TS/DIN EN 60228 CLASS 5 electrolytic twisted copper |
Insulation | Special halogen free material resistant to fire |
Stranding | Cores are twisted in layers at regular intervals. |
Insulation Colors | DIN 47100 |
Separating Wrapping | PES TAPE |
Protective Sheath | Glass fiber sheath |
Sheath | HFFR, HM4, VDE 0207-24, RAL 2003 Orange |
Sheath Color | RAL 2003 Orange |
Technicial Specifications | |
Conductor Resistance | 0.14 mm² = 148 Ω.Km |
0.22 mm² = 96 Ω.Km | |
0.25 mm² = 79.9 Ω.Km | |
0.34 mm² = 56 Ω.Km | |
0.50 mm² = 39 Ω.Km | |
0.75 mm² = 26 Ω.Km | |
1.00 mm² = 19.5 Ω.Km | |
1.50 mm² = 13.3 Ω.Km | |
2.50 mm² = 7.98 Ω.Km | |
Insulation Resistance | > 200 MΩ.Km |
Operating voltage | 0.14 mm² = 350 V |
≥ 0.22 mm² = 500 V | |
Operating temperature | -30°C ~ +70°C |
min. Bending Radius | Fixed Fixed Laying 6,5 x D |
Movable Flexible 15 x D | |
Flame Test | IEC 60332-1-2 & TS/DIN EN 50266-2-4 |
Smoke Density | IEC 61034-2 & TS/DIN EN 50268-2 |
Corrosive Gas Test | IEC 60754-1/2 & TS/DIN EN 50267-2 |
Insulation Continuity | IEC 60331, VDE 0472-814 |
Mechanical Impact Fire Resistance | DIN EN 50200; PH30-PH60-PH90 |
Current Discontinuity to the System | DIN 4102-12 ; PH90-PH120 |
Reviews
Be the first to review this item
There are no reviews yet