Description
These cables can be used as control or signal cables for computer systems and electronic control equipment. They are not for use in external or underground applications. The copper screen, which is wrapped around the PVC cores, provides protection against any external against any external electronic effects.
Cable structure | |
Conductor | IEC 60228 S 5 TS/DIN EN 60228 CLASS 5 Electrolytic strander copper |
Insulation | DIN VDE 0207 - YI2 PVC |
Stranding | Cores are twisted in layers at regular intervals |
Color Code | DIN 47100 |
Color Code(LIYY-OZ & LIYY-JZ) | DIN VDE 0293; TSE EN 50334; White numerical code on black insulation |
Seperator | PES BANT |
Screen | Tinned copper braid |
Sheath | DIN VDE 0207 Bölüm 5 RAL 7032 |
Technicial Specifications | |
Conductor Resistance | 0.14 mm² = 148 Ω.Km |
0.22 mm² = 96 Ω.Km | |
0.25 mm² = 79.9 Ω.Km | |
0.34 mm² = 56 Ω.Km | |
0.50 mm² = 39 Ω.Km | |
0.75 mm² = 26 Ω.Km | |
1.00 mm² = 19.5 Ω.Km | |
1.50 mm² = 13.3 Ω.Km | |
2.50 mm² = 7.98 Ω.Km | |
Insulation Resistance | > 200 MΩ / Km |
Operating voltage | 0.14 mm² = 350 V |
≤ 0.22 mm² = 500 V | |
Test Voltage | 0.50 mm² < = 1500 V |
0.50 mm² ≥= 2000 V | |
Effective Capacity | 0.14 mm² = 90 nF/km |
0.22 mm² = 100 nF/km | |
0.25 mm² = 100 nF/km | |
0.34 mm² = 110 nF/km | |
0.50 mm² = 120 nF/km | |
0.75 mm² = 120 nF/km | |
1.00 mm² = 120 nF/km | |
1.50 mm² = 120 nF/km | |
2.50 mm² = 120 nF/km | |
Operating temperature | -30°C ~ +80°C |
Flame Test | IEC 60332-1-2 & EN 50265-2-1 |
min. Bending Radius | Fixed Fixed Laying 6,5 x D |
Movable Flexible 15 x D |
Reviews
Be the first to review this item
There are no reviews yet