Description
For use in connecting control equipment to mechanical assembly lines, conveyor belts, transportation systems and manufacturing lines.The screen, comprising of thin,tinned copper wires, is designed to transmit control signals without any interference or noise. This cable ideal for use in industrial environments and are not for outdoor or external use.
Cable structure | |
Conductor | Single Copper Wire |
Insulation | Special halogen free material resistant to fire |
Stranding | Two cores are twisted as a pair.The pairs are twisted in layers at regular intervals. |
Insulation Colors | VDE 0815 |
Separating Wrapping | PES TAPE |
Protective Sheath | Glass fiber sheath |
Screen | AL-PEs TAPE with grounding wire |
Sheath | HFFR, HM4, VDE 0207-24 |
Sheath Color | RAL 3000 RED and RAL 2003 ORANGE |
Technicial Specifications | |
Standard | VDE 0815 |
Conductor Resistance | 0.60 mm² = 64.6 Ω/Km |
0.80 mm² = 36.6 Ω/Km | |
Insulation Resistance | min. 100 MΩ.Km |
Effective Capacity | Max. 100 nF/km |
Capacity Imbalance | 300 pF / 100 m |
Operating voltage | Max. 300V |
Test Voltage | Core/Core 0.60 mm to 0.80 mm |
800 V / 1 mm > 1000 V | |
Operating temperature | -30°C ~ +70°C |
min. Bending Radius | 10 x D |
Flame Retardant Test | IEC 60332-1-2 & TS/DIN EN 50266-2-4 |
Smoke Density | IEC 61034-2 & TS/DIN EN 50268-2 |
Corrosive Gas Test | IEC 60754-1/2 & TS/DIN EN 50267-2-3 |
Insulation Continuity | IEC 60331, VDE 0472-814 |
Mechanical Impact Fire Resistance | DIN EN 50200; PH30-PH60-PH90 |
Current Discontinuity to the System | DIN 4102-12 ; PH90-PH120 |