Description
For use on computer systems, control equipments as control and signal cable.Nor for outdoor or subterranean use.Copper screen protects PVC cores.These cables are halogen free and flame retardant.
Cable structure | |
Conductor | IEC 60228 S 5 TS/DIN EN 60228 CLASS 5 Twisted electrolytic copper |
Insulation | HFFR, HI2, VDE 0207-23 |
Stranding | Cores are twisted in layers at regular intervals |
Insulation color coding | DIN 47100 |
Seperator | PES TAPE |
Screen1 | AL-PES TAPE |
Screen2 | Tinned copper braid |
Sheath | HFFR, HM2, VDE 0207-24, RAL 7001 GRİ |
Technicial Specifications | |
Conductor Resistance | 0.14 mm² = 148 Ω.Km |
0.22 mm² = 96 Ω.Km | |
0.25 mm² = 79.9 Ω.Km | |
0.34 mm² = 56 Ω.Km | |
0.50 mm² = 39 Ω.Km | |
0.75 mm² = 26 Ω.Km | |
1.00 mm² = 19.5 Ω.Km | |
1.50 mm² = 13.3 Ω.Km | |
2.50 mm² = 7.98 Ω.Km | |
Insulation Resistance | > 200 MΩ.Km |
Operating voltage | 0.14 mm² = 350 V |
≥ 0.22 mm² = 500 V | |
Effective Capacity | 0.14 mm² = 90 nF/km |
0.22 mm² = 100 nF/km | |
0.25 mm² = 100 nF/km | |
0.34 mm² = 110 nF/km | |
0.50 mm² = 120 nF/km | |
0.75 mm² = 120 nF/km | |
1.00 mm² = 120 nF/km | |
1.50 mm² = 120 nF/km | |
2.50 mm² = 120 nF/km | |
Operating temperature | -30°C ~ +80°C |
Smoke Density | IEC 61034-2 & TS/DIN EN 50268-2 |
Flame Test | IEC 60332-1-2 & EN 50265-2-1 |
Corrosive Gas Test | IEC 60754-1/2 & TS/DIN EN 50267-2-3 |
min. Bending Radius | Fixed Fixed Laying 6,5 x D |
Movable Flexible 15 x D |